<var id="pnxrj"></var>
<var id="pnxrj"><strike id="pnxrj"></strike></var>
<var id="pnxrj"></var>
<menuitem id="pnxrj"><strike id="pnxrj"></strike></menuitem>
<var id="pnxrj"></var>
<var id="pnxrj"></var>
<var id="pnxrj"><video id="pnxrj"><thead id="pnxrj"></thead></video></var>
<var id="pnxrj"><dl id="pnxrj"><progress id="pnxrj"></progress></dl></var>
<var id="pnxrj"></var><var id="pnxrj"><strike id="pnxrj"></strike></var><cite id="pnxrj"></cite>
<var id="pnxrj"><strike id="pnxrj"></strike></var>
<menuitem id="pnxrj"><dl id="pnxrj"></dl></menuitem>
<menuitem id="pnxrj"><dl id="pnxrj"><progress id="pnxrj"></progress></dl></menuitem>
<cite id="pnxrj"></cite>
<var id="pnxrj"></var><var id="pnxrj"></var><menuitem id="pnxrj"><dl id="pnxrj"></dl></menuitem>
<var id="pnxrj"></var>
<menuitem id="pnxrj"><strike id="pnxrj"></strike></menuitem>
歡迎來到上海翼中動力官方網站
上海翼中動力專業銷售柴油發電機組!

專業銷售康明斯上柴玉柴濰柴珀金斯三菱道依茨濟柴沃爾沃奔馳等品牌發電組!


News Classification

新聞中心

Contact Us

聯系我們

當前位置:上海翼中動力 > 新聞資訊 > 消防備用柴油發電機組基本要求

消防備用柴油發電機組基本要求

消防備用柴油發電機組基本要求

消防備用柴油發電機組的基本要求有以下幾點:

1、一類高層建筑自備發電機組,應設有自動起動裝置,并能在30秒內供電;

2、類消防備用柴油發電機組的要求

(1)一類高層建筑自備發電機組,應設有自動起動裝置,并能在30秒內供電;

(2)二類高層建筑自備發電機組,當采用自動起動有困難時,可采用手動起動裝置.

     當地區供電條件不能滿足消防一級負荷和二級負荷的供電可靠性要求,或從地區變電站取得第二電源不經濟時,應設置自備消防備用電源(柴油發電機組)。

13

自備消防備用電源有:應急發電機組、蓄電池組、不間斷電源裝置(UPS)、燃料電池。

高層建筑的消防自備電源對自備發電設備(自備應急發電機組)的要求有:

自備應急發電機組有柴油發電機組和燃氣輪機發電機組兩種。

   選擇柴油發電機組時,宜選用高速柴油發電機組和無刷型自動勵磁裝置。因為,高速柴油發電機組具有體積小、重量輕、起動運行可靠等優點。無刷型自動勵磁裝置具有適應各種起動方式、易于實現機組自動化或對發電機組遙控的特點,并且,當與自動電壓調整裝置配套使用時,可使靜態電壓調整率保證在士2.5%以內。

自備應急發電機組應裝設快速自動起動及電源自動切換裝置,并具有連續三次自起動的功能。對于一類高層建筑,自起動切換時間不超過30s;對于其他建筑,在采用自動起動有困難時也可采用手動起動裝置。機組一般應采用電起動,不宜用壓縮空氣起動。發電機組總臺數不宜超過2臺,單機容量一般在800kW及以下。

燃氣輪機發電機裝置包括燃氣輪機、發電機、控制屏、起動蓄電池、油箱、進氣和排氣,消音器及其他設備等。機組可分為固定型、可動型和軌道型。發電機為三相交流同期發電機、無刷交流勵磁方式。

燃氣輪機的冷卻不需水冷而用空氣自行冷卻,加之燃燒需要大量空氣,所以,燃氣輪機組的空氣需要量比柴油機組大2.5~?4倍。因此,裝設位置必須考慮進氣排氣方便的地上層或屋頂為宜,不宜設在地下層,因地下層的進氣排氣都有一定難度。